Choose Parts Below
 
Automatic Nozzle Series
Emergency Shut Valve
Reconnectable Breakaway
Angel Check Valve
Hose
Hose Coupling
Hose Swivel
Corrugated Compensator
Triangular Flange
   
Emergency Shut-off Valve are installed on fuel supply lines beneath at grade level to minimize hazards associated with collision or fire at the dispenser. If the dispenser is pulled over or dislodged by collision, the top of the valve breaks off the flow of fuel. Single-poppet models shut off supply flow, while double-poppet models shut off supply as well as prevent release of fuel from the dispenser's internal piping. The base of the Emergency Valve is securely anchored to the concrete dispenser island through as a stabilizer bar system within a U-Bolt Assembly. Valve inlet (bottom) connection are female pipe threads and outlet (top) connections are available with female threads, male threads, or a union fitting. Other options include suction system models with a normally closed secondary poppet which maintain prime, and models with external threads on inlet body which connect to secondary containment system.
   
 
  • Body : cast iron(Spray-paint)
    Surface : electronic Nickel plated
    Seal : Buna-N O-ring

Net Weight : 18kg/case of 6
Gross Weight : 20kg/case of 6
37.5x13.5x39cm3/case of 6
 
           
         
Flow rate: 0-120 L/M
• Working pressure: 0.2Mpa
• Valve closing speed: 0.5s
• Lowest shut-off temperature: 75 degrees Celsius.
• Medium: water, gasoline, diesel and kerosene.
• Operating Environment: -30~+55 degrees Celcius.
• Fire Protection- a fusible link trips the valve closed at 75 to shut off fuel supply to the dispense.
• Integral Test Port – a 3/8” Test Port allows the piping system to be air tested without breaking any piping connection.
• Low-Profile Tops-Female and Union-top double poppet valves have a low-profile top to allow upgrading from single-poppet valves without changing existing piping.
• 100% Factory Tested.

 